Regenerative power supply modules

General data and operating conditions

7

264

EDS94SPP101-7.1

Mounting conditions
Mounting place

In the control cabinet

Mounting position

Vertical

Mounting clearances

Above/below

80 mm / ≥ 120 mm

Observe the device-related

notes on mounting.

To the sides

Side-by-side mounting without

any clearance

Supply conditions for the regenerative power supply module
AC mains operation

Connection at the assigned mains filter

DC-bus operation

Direct connection of the axis modules via terminals or

busbar systems

See the chapter on DC-bus operation in the Hardware

Manual for further information.

Environmental conditions
Climate

Storage

IEC/EN 60721-3-1

1K3 (-25 ... +60 °C)

Transport

IEC/EN 60721-3-2

2K3 (-25 ... +70 °C)

Operation

IEC/EN 60721-3-3

3K3 (-10 ... +55 °C)

Current derating at +45 ... +55 °C:

Device size 1 ... 7: 2.5 %/°C

Device size 8S ... 10: 1 %/°C

Site altitude

0 ... 4000 m amsl

1000 ... 4000 m amsl: current derating of 5 %/1000 m

Pollution

EN 61800-5-1

Degree of pollution 2

Vibration resistance

(9.81 m/s

2

= 1 g)

Transport

IEC/EN 60721-3-2

2M2

EN 61800-2

2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s

2

200 ... 500 Hz: acceleration resistant up to 15 m/s

2

Operation

Germanischer Lloyd

5 ... 13.2 Hz: amplitude ±1 mm

13.2 ... 100 Hz: acceleration resistant up to 0.7 g

IEC/EN 60068-2-6

10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g