SECTION 2 - Meter Configuration

Note: Disconnect the pulse input terminal block.

Reset Meter: Click the Reset Meter button to reset all data fields to zero.

Units: Enter units of measure. Example: KWH, GPM, LPM, CFM, BTUH, MWH, etc.

Maximum 5 alpha and/or numeric characters (uppercase and/or lowercase).

2.5.0

2.5.1

2.5.2

2.5.3

2.5.4

© Copyright 2009

DN IS-IPSM101.1

® Registered trademark MAMAC SYSTEMS, Inc.

11 of 17

Caution: Before starting the IP Sub Metering Appliance, please insure that the time and date

are configured to maintain data integrity.

Constant: Input the meter constant. The meter constant is the value per pulse. For

example, if each pulse is equal to 100 Watts and the unit of measure is KWH, the meter

constant will be 0.100. Similarly, if the water meter gives a pulse each gallon of flow per

minute and the units are GPM, the meter constant will be 1.000. Meter constant can be from

0.001 to a maximum of 9.999.

12:57:39

May 1, 2009

IP Sub Metering Appliance:

Main
Data Logging

Configuration

UNO Meter

Configuration | Meter

Copyright 2009

c

www.mamacsys.com

R

Registered trademark MAMAC Systems, Inc.

METER CONFIGURATION

Constant:

1.000

Units:

KWH

Reset Meter

Save

Save: Click to save.

2.5.5

Note: Re-connect the pulse input terminal block. The IP Sub Metering Appliance is now

ready to log data.