SECTION 2 - Initial Configuration

Figures 4A and 4B

IP Sub Metering

Appliance

Ethernet Hub

Laptop/PC

Configuration 2

Cat 5 Patchcord Cable

Laptop/PC

Configuration 1

Cat 5

Crossover

Cable

IP Sub Metering

Appliance

Figure 4B

Figure 4A

For first time start-up, a laptop/PC and a crossover cable is required. If a crossover cable is not

available, a hub can also be used as shown in Figure 4B. Terminate the appliance as shown in Figure 3.

Unplug the input and output terminal blocks and leave only the power terminal block plugged in.

Attach the crossover cable to the appliance and the other end to the laptop ethernet jack as shown in

Figure 4A. If using a hub, attach a CAT 5 patchcord between the appliance and the hub and another

CAT 5 patchcord between the hub and laptop as shown in Figure 4B.

Turn the power on. The Power LED will come on. After 10 seconds the Heartbeat LED will start

blinking at one pulse per second rate. The Link LED should light up if the appliance is correctly

connected to the laptop/PC.