INPUT SPECIFICATIONS

Voltage Range:

0 to +5 VDC

Input Resolution:

12 Bit or 0.00122V

A/D Converter Typical Total Unadjusted Error

+ 1 LSB

Accuracy (Temperature)

+1°F typical using 2.8K temperature sensor

Accuracy (4–20mA)

+1.25%

Min/Max Input Voltage

-0.5VDC to +5.5VDC

Max Pulse Frequency

1.0Hz

Noise Filtering

2300Hz low pass filter

-20db/Decade