Strain relief, Installing output expansion cards, Relay output specifications – Sensaphone Express II User Manual

Page 30

Advertising
background image

28

Sensaphone

®

Express II User’s Manual

STRAIN RELIEF

Strain relief clamps are provided on the Express II enclosure to prevent wiring from being
pulled from the circuit board or damaged when passing through the enclosure. To use the strain
relief, thread wires through the clamp and the clear rubber bushing. Position the bushing in the
clamp and tighten the screws on either side so that the wiring does not move. See Figure 13.

Figure 13: Strain relief clamp

INSTALLING OUTPUT EXPANSION CARDS

To install an output expansion card:

1. Turn the unit off. Damage may occur to the motherboard or to the output card if installed

while power is still on.

2. Remove the screws and blank plate of the first available slot from left to right.

NOTE: Always install cards side by side—do not skip a slot.

3. Hold the card with the LEDs at the top with the DIN connector plug on the card lined up with

the DIN connector socket on the motherboard.

4. Insert the DIN connector plug into the DIN connector socket and press down slightly to

connect.

5. Turn the unit on.

Wire the outputs for the configuration you want—manual or auto—as described above. See
Chapter 5 for programming information.

NOTE: When installing a combination of input and output cards, always install the input cards

grouped together in the left slots and the output cards to the right of them. If you install an
input expansion card after an output card has been installed, you must disconnect the output
card, install the input card in its place, and reinstall the output card to the right of it.

RELAY OUTPUT SPECIFICATIONS

TYPE:

Latching, SPST

Related Load:

2A at 250VAC

2A at 30VDC

Carry Current:

2A

Maximum Operating Voltage:

250VAC

125VDC

Maximum Operating Current:

2A (AC/DC)

Maximum Switching Capacity:

500VA, 60W