System [0, System, System parameters – Sensaphone Express II User Manual

Page 50

Advertising
background image

48

Sensaphone

®

Express II User’s Manual

SYSTEM [0]

The following parameters determine the functioning
of various system features.
1. Password—The password is a security feature that
you may program to prevent unauthorized access to
Express II’s programming. The password may be any
combination of up to 6 digits.
2. Date and Time—Setting the current date and
precise time is critical for operation of various
features of the Express II. For example, to make
proper use of the alarm calling schedule and any data
logging, the unit Clock must be set.
3. Acknowledgment Code—(default: 555) The
acknowledgment code is the number, up to 6 digits,
you enter when you acknowledge an alarm using a
Touch-Tone phone. This code is also used when you
call Express II back using a Touch-Tone phone to
acknowledge an alarm.

NOTE: This code cannot be

used from a pulse (rotary) phone.
4. Halt Mode Delay time—Halt mode allows you
to disable all inputs and prevent dial out for a user-
programmed time. Halt mode is useful if you must
perform periodic tests or other activities that would
trip false alarms and initiate dial out. Halt mode can
be programmed from 0 seconds to 12 hours.

NOTE: If you program the halt mode time to zero, the
halt mode feature is disabled. The default is 1 hour.

5. Callback Acknowledgment—This feature
determines whether you can simply call Express II
back to acknowledge an alarm or if you must also
enter the acknowledgment code. When callback
acknowledgment is enabled, you may acknowledge
an alarm from either a pulse or Touch-Tone phone.
No code needs to be entered. After receiving the
alarm call, you just call the unit back. When callback
acknowledgment is disabled, you must use a Touch-
Tone phone to acknowledge the alarm by entering
the acknowledgment code, or else acknowledge the
alarm locally.

Note that with Callback enabled, the unit will not
answer until the phone has rung

10 times, regardless

of what number of rings the alarm feature is set to.
(See also “Unit Configuration” below.)

SYSTEM PARAMETERS

1) Press Program.

2) Press System.

3) System menu will be displayed.

1-Password:

1) Press

1 to program password.

2) Enter password.(up to 6 digits)

The default is no password.

2-Date and time:

1) Press

2 to set Clock.

2) Enter: day, month, year, hours,

minutes, seconds, and day of the
week.

3-Acknowledgment code:

1) Press

3 for Acknowledgment Code.

2) Enter code. (6 digits; the default is

“555”)

4-Halt mode delay time:

1) Press

4 for Halt Mode Delay Time.

2) Enter minutes.

5-Callback acknowledgment:

1) Press

5 for Callback Acknowledge.

2) Enter

1 to enable.

Enter

0 to disable.

Advertising