Current Share Boards - Optional Feature (Cont.)

Please note: The CSB is not intended for use in Hotswap Applications.

Requirements:
1.
For proper operation, the power supplies being paralleled should be enabled at the
same time.
2. -Out conductors must be of equal length and wire gauge. Separate -Out conductors
must be used from each supply to the load, or the use of a "Y" connection to a

common point must be used as shown in figure 1. Each leg of the "Y" must have a
minimum of a few millivolts of drop in order for proper operation. 50 mV to 100 mV
of drop will provide from 5% to 1% accuracy.
3. -V1 and -V2 for all Box-to-Box circuits must be connected directly at the negative
output power studs or terminals to achieve accurate current sharing.
4. D* can be added if redundancy is needed. If redundancy is not required, D* can be
replaced with direct wire connections.
5. When using D*, the Power input should be connected on the cathode side of the

paralleling diodes as shown above.
6. Terminate Sense Leads either locally or remotely as shown in figure 1.
7. For paralleling more than 2 supplies consult factory for assistance.

Figure 1. CSB Interconnect Example

Power Supply 1

24V@1kW

+OUT

+S

-OUT

-S

TRIM

Power Supply 2

24V@1kW

+OUT

+S

-OUT

-S

TRIM

T1
-V1
T2
-V2

Power

+VOUT

-VOUT

D*

D*

CSB02

Black

White

Brown

Yellow

Red

Figure 12.

CSB Interconnect Example