For Non-Regenerative drives only, remove the bolt and washers that

secure the U and W phase power terminals to the internal armature
circuit fuses and while pulling the U and W phase power terminals up
and into the drive, slide the AC Current Transducers off of the
terminal bus bars and out of the drive.

Step 4: Install the New AC
Current Transducers

Install the new AC Current transducers in reverse order of removal as
detailed in Step 3: .

Remove the Existing AC Current Transducers on page 5

.

Important: Note the color and location of the signal wires to ensure that

each wire is properly connected during installation. The wires
connected to the left CT are red and white and the wires
connected to the right CT are blue and black.

Non-Regenerative drive

Remove bolts,
washers and
terminal

Slide AC
Current
Transducers
off of bus bars

Left AC Current Transducer

Right AC Current Transducer

Left CT - red
and white wires

Right CT - blue
and black wires