Installation and Wiring

Chapter 3

Port Assignment

• When used in an Integrated Motion application, the Safe Torque Off

option must be installed in port 6.

• Only one safety option module can be installed at a time. Multiple safety

options or duplicate safety option installations are not supported.

Jumper Settings

• Ensure the hardware enable jumper (ENABLE) on the main control board

is installed. Refer to

page 21

for location. If not installed, the drive will

fault when powered up.

• Ensure the safety enable jumper (SAFETY) on the main control board is

removed (Frames 1…7 only). Refer to

page 20

for location.

Verify Operation

Test the safety function for proper operation after initial installation of the Safe
Torque Off option module. Retest the safety function at the intervals determined
by the safety analysis described on

page 15

.

Verify that both safety channels are functioning according to

Table 3

.

Table 3 - Channel Operation and Verification

Safety Function Status

Drive In
Not Enabled
State

Drive In
Not Enabled
State

Drive In
Not Enabled
State

Drive Able
To Run (Ready)

Safety Channel Operation

Safe Torque Off Option
Terminals SP+ & SP-
(Safety Power)

No Power Applied

Power Applied

No Power Applied

Power Applied

Safe Torque Off Option
Terminals SE+ & SE-
(Safety Enable)

No Power Applied

No Power Applied

Power Applied

Power Applied

IMPORTANT

If an external fault is present on the wiring or circuitry controlling the Safety
Enable or Safety Power inputs for a period of time, the Safe Torque Off option
will not detect this condition. When the external fault condition is removed the
Safe Torque Off option will allow an enable condition.

To achieve maximum safety rating, both safety inputs SP and SE must be
activated by appropriate dual channel equipment. The repeated activation of
the safety function by only one input at a time may result in a spurious
detection of a fault.

TIP

No tell back contact for status is provided on the Safe Torque Off option.