Circuit status, Operating principle, Fault detection – Rockwell Automation 21G PowerFlex 750 Series Safe Torque Off User Manual

Page 29: Figure 2 - stop category 0 – coast

Advertising
background image

Rockwell Automation Publication 750-UM002F-EN-P - July 2013

29

Description of Operation

Chapter 4

Example 1 - PowerFlex 750-Series Drives, Frames 1…10 Safe Torque
Off Connection with Coast-to-Stop Action, Dual Channel

Figure 2 - Stop Category 0 – Coast

Circuit Status

Circuit shown with guard door closed and system ready for normal drive
operation.

Operating Principle

This is a dual channel system with monitoring of the Safe Torque Off circuit and
drive. Opening the guard door will switch the input circuits (S11-S12 & S21-
S22) to the Minotaur monitoring safety relay unit. The output circuits (13-14 &
23-24) will cause the Safe Torque Off option and drive Enable circuit to trip and
the motor will coast to stop. To restart the drive, the Minotaur safety relay must
first be reset followed by a valid start command to the drive.

Fault Detection

A single fault detected on the Minotaur safety input circuits will result in the
lock-out of the system at the next operation and will not cause loss of the safety
function.

A1 S21 S11 S52 41 13 23 33

A2 S22 S12 S34 42 14 24 34

Minotaur

MSR127TP

GuardMaster

Trojan

SP+

SE+

Sd

SP–

SE–

Sd

Gate

E-Stop

Latching

Button

24V DC

Common

External

+24V DC

AC Line

Input Power

Motor

Gate Control

Circuit

Gate Control

Power Supply

Jumpers:
ENABLE Installed
SAFETY Removed

24V DC Common

Start/Stop Common

Start

Stop

+24V DC

PowerFlex

750-Series

Stop

Start

External

+24V DC