Specifications, Introduction, General specifications – Rockwell Automation 21G PowerFlex 750 Series Safe Torque Off User Manual

Page 33: Appendix a, Introduction general specifications, Appendix

Advertising
background image

Rockwell Automation Publication 750-UM002F-EN-P - July 2013

33

Appendix

A

Specifications

Introduction

This appendix provides general specifications for the Safe Torque Off Option
module.

General Specifications

Attribute

Value

Standards

IEC 60204-1, IEC 61508, IEC 61800-3, IEC 61800-5-1, IEC 61800-5-2, IEC 62061,
ISO 13489

Safety category

Cat. 3 and PL e per ISO 13849-1;
SIL CL3 per IEC 61508 and EN 62061

Power supply (user I/O)

24V DC ±10%, 0.8…1.1 x rated voltage

(1)

PELV or SELV

(1) Safety outputs need additional fuse for reverse voltage protection of the control circuit. Install a 6 A slow-blow or 10 A fast-acting

fuse.

Power consumption

4.4 watts

Safety enable SE+, SE–

24V DC, 25 mA

Safety power SP+, SP–

24V DC, 45 mA

Input ON Voltage, min

24V DC ±10%, 21.6…26.4V DC

Input OFF Voltage, max

5V

Input OFF Current, max

2.5 mA @ 5V DC

Conductor type

Multi-conductor shielded cable

Conductor size

(2)

(2) Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

0.3…0.8 mm

2

(28…18 AWG)

Strip length

10 mm (0.39 in.)