Circuit status, Operating principle, Application considerations – Rockwell Automation 21G PowerFlex 750 Series Safe Torque Off User Manual

Page 30: Figure 3 - stop category 0 – coast

Advertising
background image

30

Rockwell Automation Publication 750-UM002F-EN-P - July 2013

Chapter 4

Description of Operation

Example 2 - PowerFlex 750-Series Drives, Frames 1…10 Safe Torque
Off Connection with Coast-to-Stop Action, Dual Channel

Figure 3 - Stop Category 0 – Coast

Circuit Status

Circuit shown with guard door closed and system ready for normal drive
operation.

Operating Principle

This is a dual channel system with monitoring of the Safe Torque Off circuit and
drive. Opening the guard door will switch the input circuits (S11-S12 & S21-
S22) to the Minotaur monitoring safety relay unit. The output circuits (13-14 &
23-24) cause the drive Enable circuit to trip and the motor will coast to stop. To
restart the drive, the Minotaur safety relay must first be reset followed by a valid
start command to the drive.

Application Considerations

When the hazard analysis for the overall machine determines the need for
external mechanical brakes or other stopping means, the external means shall be
activated after the removal of power for Stop Category 0.

If the Safe Torque Off option sticks ON, the motor will stop on command due to
the enable input. The system cannot be reset when this fault condition exists.

GuardMaster

Trojan

A1

S21 S11 S52 S12

A2 X1 X2

13 23

14 24

S33

Y2

S34

Y1

X3

37 47 57

38 48 58

X4

S22

Y39 Y40

Minotaur

MSR138DP

SP+

SE+

Sd

SP–

SE–

Sd

Gate

24V DC
Common

External

+24V DC

AC Line

Input Power

Motor

Gate Control

Circuit

Gate Control

Power Supply

Jumpers:
ENABLE Installed
SAFETY Removed

24V DC Common

Start/Stop Common

Start

Stop

+24V DC

PowerFlex

750-Series

Stop

Start

External

+24V DC