Rockwell Automation 1606-XLP15B Power Supply Reference Manual User Manual

Page 11

Advertising
background image

All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.

Rockwell Automation Publication 1606-RM020A-EN-P — March 2014

11

Bulletin 1606 Switched Mode Power Supplies

13. EMC

The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions. A detailed EMC report is available on request.

EMC Immunity

Generic standards: EN 61000-6-1 and EN 61000-6-2

Electrostatic discharge

EN 61000-4-2

Contact discharge
Air discharge

8kV
8kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz-2.7GHz

10V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

Input lines
Output lines

4kV
2kV

Criterion A
Criterion A

Surge voltage on input

EN 61000-4-5

L N
N PE, L PE

2kV
4kV

Criterion A
Criterion A

Surge voltage on output

EN 61000-4-5

+ -
+ PE, - PE

500V
2kV

Criterion A
Criterion A

Conducted disturbance

EN 61000-4-6

0.15-80MHz

10V

Criterion A

Mains voltage dips

EN 61000-4-11

0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac

40% of 200Vac
70% of 200Vac

0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms

Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A

Voltage interruptions

EN 61000-4-11

0Vac, 5000ms

Criterion C

Input voltage swells

Rockwell Automation internal standard

300Vac, 500ms

Criterion A

Powerful transients

VDE 0160

over entire load range

750V, 1.3ms

Criterion A

Criteria:

A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply may shut down and restarts by itself. The power supply will incur no damage or

hazard.

EMC Emission

Generic standards: EN 61000-6-3 and EN 61000-6-4

Conducted emission

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22

Class B, input lines

Radiated emission

EN 55011, EN 55022

Class B

Harmonic input current

EN 61000-3-2

Not applicable below 75W
input power

Voltage fluctuations, flicker

EN 61000-3-3

fulfilled

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

Switching frequency

Constant, typ. 65kHz

Advertising