background image

All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.

Rockwell Automation Publication 1606-RM020A-EN-P — March 2014

21

Bulletin 1606 Switched Mode Power Supplies

20.10. Use in a Tightly Sealed Enclosure

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.

The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.

The power supply is placed in the middle of the box; no other heat producing item is inside the box.

Enclosure:

Rittal Type IP66 Box PK 9510 100, plastic, 130x130x75mm

Input:

230Vac

Case A:
Load:

12V,

1.3A;

load

is

placed

outside

the

box.

Temperature inside the box:

38.9°C (in the middle of the right side of the power supply with a distance of 1cm)

Temperature outside the box:

28.0°C

Temperature rise:

10.9K

Case B:
Load:

12V, 1.05A; (=80%) load is placed outside the box.

Temperature inside the box:

33.9°C (in the middle of the right side of the power supply with a distance of 1cm)

Temperature outside the box:

27.4°C

Temperature rise:

8.5K

Advertising