Operation on two phases, Use without pe on the input – Rockwell Automation 1606-XLP15B Power Supply Reference Manual User Manual

Page 20

Advertising
background image

All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.

20

Rockwell Automation Publication 1606-RM020A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

20.8. Operation on Two Phases

2

4

0V

+10%

max.

Fuse

L2

L1

L3

L

N

PE

Power Supply

AC

DC

internal

fuse

The power supply can also be used on two phases of a three-phase-system.
Such a phase-to-phase connection is allowed as long as the supplying
voltage is below 240V

+10%

. Use a fuse or a circuit breaker to protect the N

input. The N input is not protected internally; in this case, it is connected
to a hot wire. Appropriate fuses or circuit breakers are specified in section
20.4, “External Input Protection”.

20.9. Use Without PE on the Input

From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2.
Contact Rockwell Automation if you do not use the PE terminal. A different marking of the front foil is then required.

Grounding of the input is beneficial for a high EMI immunity: symmetrical spikes or fast transients on the input side
can be conducted directly to earth by the built-in filter capacitors. The magnitude of such spikes or fast transients on
the output side caused by the input is much smaller compared to not connecting this terminal to the ground.

Fig. 20-3 Grounded input

Fig. 20-4 Ungrounded input

Surge

Y

X

L

N

Ground

Power Supply

+

-

Surge

X

L

N

Power Supply

+

-

24V

Spike