All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.

22

Rockwell Automation Publication 1606-RM020A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

20.11. Mounting Orientations

Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the max. allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:

Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).

Fig. 20-5
Mounting
Orientation A
(Standard
orientation)

Power

Supply

OUTPUT

INPUT

Output Power

0

10

20

30

40

60°C

3

9

12

15W

50

A1

6

Ambient Temperature

Fig. 20-6
Mounting
Orientation B
(Upside down)

Power

Supply

OUTPUT

INPU

T

Output Power

0

10

20

30

40

60°C

3

9

12

15W

50

6

A1

A2

Ambient Temperature

Fig. 20-7
Mounting
Orientation C
(Table-top
mounting)

Output Power

0

10

20

30

40

60°C

3

9

12

15W

50

6

A1

A2

Ambient Temperature

Fig. 20-8
Mounting
Orientation D
(Horizontal cw)

Power

Supply

OUTPUT

IN
PU
T

Output Power

0

10

20

30

40

60°C

3

9

12

15W

50

6

A1

A2

Ambient Temperature

Fig. 20-9
Mounting
Orientation E
(Horizontal ccw)

Pow

er

Supp

ly

OUTP

UT

IN

PUT

Output Power

0

10

20

30

40

60°C

3

9

12

15W

50

6

A1

A2

Ambient Temperature