Hold-up time – Rockwell Automation 1606-XLP15B Power Supply Reference Manual User Manual

Page 7

Advertising
background image

All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.

Rockwell Automation Publication 1606-RM020A-EN-P — March 2014

7

Bulletin 1606 Switched Mode Power Supplies

7. Hold-up Time

AC 100V

AC 120V

AC 230V

Hold-up Time

typ.

62ms

96ms

365ms

at 12V, 0.65A, see Fig. 7-1

typ.

30ms

46ms

191ms

at 12V, 1.3A, see Fig. 7-1

Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on at this time.

Fig. 7-1 Hold-up time vs. input voltage

Fig. 7-2 Shut-down behavior, definitions

0

25

50

125

150ms

85

120

155

190

230Vac

Input Voltage

Hold-up Time

75

100

a) 12V 0.65A typ.

b) 12V 0.65Amin.
c) 12V 1.3A typ.
d) 12V 1.3A min.

a

b

c

d

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Input