Dielectric strength – Rockwell Automation 1606-XLP15B Power Supply Reference Manual User Manual

Page 14

Advertising
background image

All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.

14

Rockwell Automation Publication 1606-RM020A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

17. Dielectric Strength

The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.

Fig. 17-1 Dielectric strength

A B C

Type test

60s

2500Vac

3000Vac

500Vac

Factory test

5s

2500Vac

2500Vac 500Vac

Field test

5s

2000Vac

2000Vac

500Vac

Cut-off current setting

> 6mA

> 6mA

> 1mA

A

C

N

L

Input

Earth, PE

Output

-

+

B


To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit be connected to the protective earth system.
This helps to avoid situations in which a load starts
unexpectedly or cannot be switched off in the occurence of
unnoticed earth faults.