Programming Parameters

The following table provides the option-specific parameters that are
provided with each control option. These parameters are in addition to
those already discussed in the Basic Set Up and Metering groups.
Diagrams supporting the options described below are shown later in this
chapter.

Option

Parameter

Range

Standard

SMC Option

This parameter identifies the type of

control present and is not user

programmable.

Standard

Soft Stop

Soft Stop Time

Allows the user to set the time

period for the soft stopping function.

0…120 s

SMC Option

This parameter identifies the type of

control present and is not user

programmable.

Standard

Slow Speed Select

Allows the user to program the slow

speed that best fits the application.

Low: 7% – Forward,

10% – Reverse

High: 15% – Forward,

20% – Reverse

Slow Speed Direction

This parameter programs the slow

speed motor rotational direction.

Forward, Reverse

Slow Accel Current

Allows the user to program the

required current to accelerate the

motor to slow speed operation.

0…450% of full load current

Preset

Slow Speed

Slow Running Current

Allows the user to program the

required current to operate the

motor at the slow speed setting.

0-450% of full load current

Pump Control

SMC Option

This parameter identifies the type of

control present and is not user

programmable.

Pump Control

Pump Stop Time

Allows the user to set the time

period for the pump stopping

function.

0…120 s

Pump Control

Starting Mode

Allows the user to program the

SMC-Flex controller for the type of

starting that best fits the application.

Pump Start, Soft Start,

Current Limit Start,

Full Voltage