1-6

Product Overview

% 5-" %. 0

Starting Modes (cont.)

Preset Slow Speed

This option can be used in applications that require a slow-speed jog for
general purpose positioning. Preset Slow Speed provides either 7% of
base speed (low) or 15% of base speed (high) settings in the forward
direction. Reverse can also be programmed and offers 10% of base speed
(low) and 20% of base speed (high) settings.

Run

Forward

15% – High

7% – Low

10% – Low

20% – High

Reverse

Time (seconds)

Start

Run

Run

Forward

15% – High

7% – Low

10% – Low

20% – High

Reverse

Time (seconds)

Start

Forward

15% – High

7% – Low

10% – Low

20% – High

Reverse

Time (seconds)

Start

Figure 1.6 – Preset Slow Speed Option

Important: Slow speed running is not intended for continuous operation due
to reduced motor cooling. The two starts per hour limitation also applies to
slow speed operation. This option employs a cycle-skipping scheme which
produces limited torque. Applications should be checked with the factory.