8-8

Communications

1560E-UM050B-EN-P - June 2013

SMC-Flex Bit Identification

Table 8.G – Logic Status Word

Bit #

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Status

Description

X

Enabled 1 – Control Power Applied

0 – No Control Power

X

Running 1 – Power Applied to Motor

0 – Power not Applied to Motor

X

Phasing 1 – ABC Phasing

0 – CBA Phasing

X

Phasing

Active

1 – 3-phase is valid

0 – No valid 3-phase is detected

X

Starting

(Accel)

1 – Performing a Start Maneuver

0 – Not performing a Start Maneuver

X

Stopping

(Decel)

1 – Performing a Stop Maneuver

0 – Not performing a Stop Maneuver

X

Alarm

1 – Alarm Present

0 – No Alarm Present

X

Fault

1 – Fault Condition Exists

0 – No Fault Condition

X

At Speed 1 – Full Voltage Applied

0 – Not Full Voltage Applied

X

Start/

Isolation

1 – Start/Isolation Contactor Enabled

0 – Start/Isolation Contactor Disabled

X

Bypass

1 – Bypass Contactor Enabled

0 – Bypass Contactor Disabled

X

Ready

1 – Ready

0 – Not Ready

Bits 12 to 15 – Not Used

Table 8.H – Logic Command Word

Bit #

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Status

Description

X

Stop

1 – Stop/Inhibit

0 – No Action

X

Start

1 – Start

0 – No Action

X

Option #1

Input

1 – Stop Maneuver/Inhibit

0 – No Action

X

Clear

Faults

1 – Clear Faults

0 – No Action

X

Option #2

Input

1 – Perform Option 2 function

0 – No Action

Bits 5 to 15 – Not Used