Default input/output configuration, Variable input/output configuration – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 115

Advertising
background image

Communications

8-7

1560E-UM050B-EN-P - June 2013

The default configuration for I/O is 4 bytes in and 4 bytes out (TX =
4 bytes, RX = 4 bytes) and is arranged according to the following table.

Table 8.E

Produced Data

(Status)

Consumed Data

(Control)

Word 0

Logic Status

Logic Command

Word 1

Feedback Ê

Reference v

Ê

The feedback word is always Current in Phase A.

Ë

The reference word is not used with the SMC-Flex, however the space must be

reserved.

The SMC-Flex supports 16-bit DataLinks. Therefore, the device can be
configured to return additional information. The I/O message size depends
on how many DataLinks are enabled. The following table summarizes the
I/O data sizes.

Table 8.F

Data Links

Rx

Size

Tx

Size

Logic Status/

Command

(16-bit)

Reference/

Feedback

(16-bit)

A

B

C

D

4

4

X

X

8

8

X

X

X

12

12

X

X

X X

16

16

X

X

X X X

20

20

X

X

X X X X

To configure DataLinks, refer to Configuring Data Links on page 8-10.

Default Input/Output
Configuration

Variable Input/Output
Configuration

Advertising