Protection and diagnostics, Overload – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 19

Advertising
background image

Product Overview

1-9

Protection and Diagnostics

The MV SMC-Flex™ controller is capable of providing the following
protective and diagnostic features:

Overload

The MV SMC-Flex controller meets applicable requirements as a motor
overload protection device. Thermal memory provides added protection
and is maintained even when control power is removed. The built-in
overload algorithm controls the value stored in Parameter 12, Motor
Thermal Usage (see Chapter 4, Programming). An Overload Fault will
occur when this value reaches 100%. The parameters below provide
application flexibility and easy setup.

Parameter

Range

Overload Class

Off, 10, 15, 20, 30

Overload Reset

Manual – Auto

Motor FLC

1.0 – 1000.0 amps

Service Factor

0.01 – 1.99

Important: During slow speed operations, current waveforms exhibit
non-sinusoidal characteristics. These non-sinusoidal characteristics
inhibit the controller's current-measurement capability. To compensate
for additional motor heating that may result, the controller uses motor
thermal modeling, which increments motor thermal usage. This compen-
sation takes place when the Preset Slow Speed option is used.

Notes:

1. The factory default setting for Overload Class, which is "OFF", disables

overload protection. An overload trip class and the motor's full-load
current rating must be programmed to enable overload protection.

2. If the MV SMC-Flex is used to control a multi-speed motor, or more

than one motor, the Overload Class parameter must be programmed
to "OFF" and separate overload relays must be supplied for each
speed/motor.

3. Automatic reset of an overload fault requires the start input to be

cycled in a 2-wire control scheme.

4. The trip rating is 117% of the programmed FLC.

Figures 1.9 and 1.10 provide the overload trip curves for the available trip
classes.