Operational Procedure

The machine operator should not use the SLS to perform a normal stop
function. The SLS should only be used to isolate the system. Machine access is
allowed only after the SLS switch is locked and tagged in the OFF position and
the white SAFE light is illuminated to verify that the system is indeed isolated.
If the white SAFE light fails to illuminate when the SLS switch is turned to the
OFF position, the machine cannot be considered isolated nor safe. The
operator should not enter the machine, but should contact a SLS qualified
service technician.

Component Function and
Description

Table 3.A SLS Box

Component

Cat. No.

Source

Description

Repairable

Function

Enclosure

32267-121-51

Allen-Bradley

See-through cover

Provides segregation and
protection of the SLS
components.

Mounting plate

32267-122-02

Allen-Bradley

Mounts equipment.

Control
transformer

B075-1017-GA

Micron

480/400 – 120/110V

No

Provides 120V for control circuit.

Primary fuse block

1492-FB2C30-L

Allen-Bradley

Class CC rejection type
with blown fuse indication

No

Secures fuse and indicates
status.

Primary fuses

KLDR

Allen-Bradley
or Littlefuse

Class CC fuse

No

Protects CCT primary.

Secondary fuse
block

1492-FB1C30-L

Allen-Bradley

Class CC rejection type
with blown fuse indication

No

Secures and indicates status.

Secondary fuse

KLDR

Allen-Bradley
or Littlefuse

Class CC fuse

No

Protects CCT secondary.

Power supply

PS5R-C/50W 24V

IDEC

Current limiting 24V DC
with LED

No

Provides current limited 24V DC
for SLS circuit.

Safety contactor

100S-C85D04C

Allen-Bradley

85 A IEC safety contactor,
120V coil

No

Provides isolation and status
through N.C. positive guided
auxiliary.

2 N.O. auxiliary

100-SA20

Allen-Bradley

2 N.O. auxiliary

No

Provides control circuits with
positive guidance and
monitoring of power poles.

Surge suppressor

100-FSC280

Allen-Bradley

120V RC type

No

Absorbs coil spikes.