Rockwell Automation 1000 Safety Lockout System User Manual

Page 18

Advertising
background image

Publication 1000-UM001B-US-P - July 2000

3-2 Operational Procedure

Pilz relay

PU3Z 24VDV

Pilz

Voltage supervision and
contactor monitoring
safety relay

No

Monitors position of contactor
and voltage on load side of
contactor.

Safety relay SR

700-ZBL220Z24

Allen-Bradley

24V safety relay

No

Checks for cable integrity and
for operation of the SLS switch.

Safety relay 1SR

Allen-Bradley

24V safety relay

Yes

Serves as E-stop, pilot relay, and
PLC interface.

1CR

700-CF220DJ

Allen-Bradley

24V DC control relay

Yes

Keeps safe light out if the SR
safety relay faults.

Protective cover

100-SCCA

Allen-Bradley

Protective cover

No

Prevents manual operation.

Terminal blocks

1492-H1

Allen-Bradley

Terminal blocks

No

Provides connections.

LED terminal
blocks

1492-HM2V24

Allen-Bradley

LED terminal blocks

No

Provides indication of voltage
presence.

Harting connectors

See Renewal Parts
List

Harting

Plug-in connectors

Yes

Provides quick connection and
indication of tampering if
sealed.

Table 3.A SLS Box (Continued)

Component

Cat. No.

Source

Description

Repairable

Function

Table 3.B SLS Switch

Component

Cat. No.

Source

Description

Repairable

Function

Enclosure

32267-132-51

Allen-Bradley

NEMA Type 4 SS
enclosure

Provides protection for SLS
components. Allows for tamper
indication if sealed.

Mounting plate

32267-133-01

Allen-Bradley

Mounts components

Operating handle

194R-HS4

Allen-Bradley

Lockable position
indicating operating
handle

No

Operates and provides for
lockout. Enclosure cannot be
opened when locked out.

Pilot light

800H-QR24W

Allen-Bradley

White 24V DC pilot light

Yes

Signals SAFE.

SLS switch

194E-A25-1753

Allen-Bradley

3-pole disconnect switch

No

Provides redundant signal
through safety relay.

SLS switch
auxiliary contact

194E-A-P11

Allen-Bradley

Auxiliary contact

No

Provides SLS status to PLC.

Advertising