Chapter 4: sls sequence of operation, Chapter 4, Sls sequence of operation – Rockwell Automation 1000 Safety Lockout System User Manual

Page 21: Chapter

Advertising
background image

1

Publication 1000-UM001B-US-P - July 2000

Chapter

4

SLS Sequence of Operation

The following is the sequence of operation for the SLS box and the SLS switch
as shown on Y-155798 Rev. M and Y-156328 Rev. B. The intention is to
provide an understanding of circuit operation and equipment function. This
will be an aid in troubleshooting because if the sequence stops or is
incomplete, the suspected part or failure may be narrowed down and
identified. Assumptions are made that the SLS has been installed properly, no
fuses are blown, power is on, all equipment is functioning correctly and all SLS
switches are in the ON position

A. Status

1. IC is open.
2. Power supply LED is on.
3. Pilz PU3Z power LED on.
4. All SLS switch SAFE lights are off.
5. All safety relay LEDs are on.
6. 1CR is energized (refer to cross bar).
7. Blown fuse pilot lights are off.
8. TB LEDs between + and – are on.

B. The remote 24V DC signal is applied to 1SR at TB#34 and TB#35

causing it to close the circuit between wires #4 and #5.

C. Since the safety relay 1SR is energized and its contacts between #13 and

#14 are closed, IC will be energized, actuating the IC auxiliary contacts
and sending power to the motion bus.