5-2 Troubleshooting Guide

Safety contacts
between terminals
#13 and #14 will
not close

Safety relay SR

Bad SLS switch

SLS switch

Replace SLS switch.

No

Fault, opens or
short in SLS
cable

SLS cable

Repair or replace cable.

No

1CR jammed on

1CR for operation

Replace if necessary.

No

IC jammed on

For operation

Replace entire contactor ass’y.

No

Power circuit to
safety relay open

Power LED off

Reset power supply.

Failed safety
relay

LEDs during operation

Replace.

No

Safety relay 1SR

Power circuit to
safety relay open

Power LED off

Reset power supply.

No

Failed safety
relay

LEDs during operation

Replace.

No

Won’t pick up

1CR

Open coil

Flash light coil

Replace.

No

Open circuit to
coil

Welded contacts

Replace.

No

Won’t drop out

Welded contacts

Replace.

No

Foreign material
jam

Replace.

No

Table 5.A SLS Box (Continued)