Rockwell Automation 1000 Safety Lockout System User Manual

Page 49

Advertising
background image

Publication 1000-UM001B-US-P - July 2000

Certification Documentation A-19

Table A.F LED Explanation

Item

Description

Indicator

Explanation

1

Power Supply

LED

DC on when 120V is applied

2

Control Transformer
Sec. Fuse

Blown
Fuse

On when fuse is blown

3

Control Transformer
(2) Pri. Fuses

Blown
Fuse

On when fuse is blown

4

Safety Relay 1SR

LED

POWER on when 24V DC is applied

CH1 on when circuit S10 to S11 is closed

CH2 on when circuit S21 to B2 is closed

K1 on when internal relay K1 is energized

K2 on when internal relay K2 is energized

5

Safety Relay SR

LED

POWER on when 24V DC is applied

CH1 on when circuit S10 to S11 is closed
because all SLS switches are in the ON
position

CH2 on when circuit S10 to S11 is closed
because all SLS switches are in the ON
position

K1 on when internal relay K1 is energized

K2 on when internal relay K2 is energized

6

Pilz Relay PVSR

LED

POWER on when 24V DC is applied

VL1-L2 on voltage L1 to L2 is above 10V

VL2-L3 on voltage L2 to L3 is above 10V

VL1-L3 on voltage L1 to L3 is above 10V

VL1-N on voltage L1 to ground is above 10V

VL2-N on voltage L2 to ground is above 10V

VL3-N on voltage L3 to ground is above 10V

SYSTEM FAILURE on when one of the eight
voltage sensing connections is open or
there is an internal fault in the PU3Z

VOLTAGE HAZARD on when measured
voltage is greater than 10V

7

++ Terminal Block

LED

On when the timer contact is closed

8

– Terminal Block

LED

On when the 24V DC power supply output is
on

9

12 Terminal Block

LED

On when IC and 1CR are off, PVSR output is
closed, and an SLS switch is off

10

Timing Relay TR

LED

On when time delay is complete and output
N.O. contact is closed