All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

10

Rockwell Automation Publication 1606-RM029A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

10. Remote Control of Output Voltage

This feature is not supported by the 1606-XLS960EE unit. Choose the 1606-XLS480E when this feature is needed.

11. Internal Data Logging

A protected microcontroller inside the power supply acquires and stores operating data during the life of the unit. The
data can be downloaded with a small tool and special software by Rockwell Automation service and repair personnel,
as well as in many instances in which the unit fails. The data allows for better troubleshooting. The events occuring
just before a failure can be analyzed much more accurately.

Acquired data:

- Family name of unit (1606-XLS), revision of firmware

- Operational hours

- Expired portion of lifetime (combination of temperature and period of time)

- Maximum ambient temperatures with timestamp (max. 47 values)

- Maximal input voltages with timestamp (max. 47 values) and type of input voltage (AC or DC)

- Failure report (various internal errors)

- Number and timestamp (max. 20 values) of input overvoltage transients

- Number and timestamp (max. 20 values) of over-temperature shut-downs

- Number of turn-on sequences

The data will be acquired with a fixed sampling rate unless the peak detectors do trigger due to an abnormal
condition. In such cases, the abnormal condition will be captured. Furthermore, data will always be acquired
shortly before the unit switches off.