All parameters are specified at 24V, 40A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM029A-EN-P — April 2014

11

Bulletin 1606 Switched Mode Power Supplies

12. Efficiency and Power Losses

AC 230V

Efficiency

typ.

94.6%

at 24V, 40A

Average efficiency

*)

typ.

93.8%

25% at 10A, 25% at 20A, 25% at 30A. 25% at 40A

Power losses

typ.

3.2W

with activated shut-down

typ.

12.0W

at 24V, 0A (no load)

typ.

29.6W

at 24V, 20A (half load)

typ.

54.8W

at

24V,

40A

(full

load)

*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%

of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.

Fig. 12-1 Efficiency vs. output current at 24V,

typ.

Fig. 12-2 Losses vs. output current at 24V,

typ.

Efficiency

8

12

16

20

24

28

32

36 40A

91

92

93

Output Current

94

95%

Power Losses

0

4

8

12 16 20 24 28

40A

10

0

30

40

50

60W

32 36

20

Output Current

Fig. 12-3 Efficiency vs. input voltage at 24V,

40A, typ.

Fig. 12-4 Losses vs. input voltage at 24V, 40A,

typ.

Efficiency

170

190

210

230

250 270Vac

92

93

94

Input Voltage

95%

Power Losses

30

35

40

45

50

55

60W

170

190

210

230

250 270Vac

Input Voltage

Advertising