All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

16

Rockwell Automation Publication 1606-RM029A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

Switching Frequencies

The power supply has four converters with four different switching frequencies included.

Switching frequency 1

105kHz

Resonant converter, nearly constant

Switching frequency 2

35kHz to 150kHz

PFC converter, input voltage and load dependent

Switching frequency 3

10kHz to 300kHz

Boost converter, output voltage and load dependent

Switching frequency 4

28kHz to 40kHz

Aux. converter, input voltage and load dependent

18. Environment

Operational temperature

*)

-25°C to +70°C (-13°F to 158°F)

reduce output power according Fig. 18-1

Storage temperature

-40 to +85°C (-40°F to 185°F)

for storage and transportation

Output de-rating

24W/°C

60-70°C (140°F to 158°F)

Humidity

**)

5 to 95% r.H.

IEC 60068-2-30

Vibration sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 1g

***)

2 hours / axis

IEC 60068-2-6

Shock

15g 6ms, 10g 11ms

***)

3 bumps / direction, 18 bumps in total

IEC 60068-2-27

Altitude

0 to 2000m (0 to 6 560ft)

without any restrictions

2000 to 6000m (6 560 to 20 000ft)

reduce output power or ambient temperature,
see Fig. 18-2
IEC 62103, EN 50178, overvoltage category II

Altitude de-rating

60W/1000m or 5°C/1000m

> 2000m (6500ft), see Fig. 18-2

Over-voltage category

III

IEC 62103, EN 50178, altitudes up to 2000m

II

altitudes from 2000m to 6000m

Degree of pollution

2

IEC 62103, EN 50178, not conductive

LABS compatibility

The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.

*) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the

unit.

**) Do not energize while condensation is present.
***) Higher levels allowed when using the wall mounting bracket 1606-XLC.

Fig. 18-1 Output current vs. ambient temp.

Fig. 18-2 Output current vs. altitude

0

-25

0

20

40

70°C

10

20

30

40

50

60A

continuous

60

Ambient Temperature

short-term (4s)

Allowed Output Current at 24V

Allowed Output
Current at 24V

0

0

2000

4000

6000m

10

20

30

40

50

60A

continuous

Altitude

for typ. 4s

A... Tamb < 60°C

B... Tamb < 50°C

C... Tamb < 40°C

A

B

C