Ac input – Rockwell Automation 1606-XLS960EE Power Supply Reference Manual User Manual

Page 4

Advertising
background image

All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

4

Rockwell Automation Publication 1606-RM029A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

3. AC Input

AC input

nom.

AC 200-240V

suitable for TN, TT and IT mains networks

AC input range

min.

170-264Vac

continuous operation

min.

110-170Vac

full

power

for

up

to

200ms

min.

0-170Vac

no damage to the unit

264-300Vac

<

500ms

Allowed voltage L or N to earth

max.

300Vac

continuous, IEC 62103

Input frequency

nom.

50–60Hz

±6%

Turn-on voltage

typ.

164Vac

steady-state value, load independent, see Fig. 3-1

Shut-down voltage

typ.

151Vac

steady-state value, load independent, see Fig. 3-1

Input current

typ.

4.6A

at 24V, 40A, see Fig. 3-3

Power factor

*)

typ.

0.96

at 24V, 40A, see Fig. 3-4

Crest factor

**)

typ.

1.65

at

24V,

40A

Start-up delay

typ.

750ms

see Fig. 3-2

Rise time

typ.

23ms

at 24V, 40A, resistive load, 0mF see Fig. 3-2

typ.

25ms

at 24V, 40A, resistive load, 40mF see Fig. 3-2

Turn-on overshoot

max.

200mV

see Fig. 3-2

*)

The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.

**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.

Fig. 3-1 Input voltage range

Fig. 3-2 Turn-on behavior, definitions

Turn-on

170V

Rated input range

V

IN

P

OUT

151V

264Vac

Shut

-down

164V

Start-up

delay

Rise

Time

Ov

ersh

oot

- 5%

Output
Voltage

Input
Voltage

Fig. 3-3 Input current vs. output load at 24V

Fig. 3-4 Power factor vs. output load at 24V

40A

4

8 12 16 20 24 28 32 36

0

1

2

3

4

5

6A

Input Current, typ.

Output Current

Power Factor, typ.

4

8 12 16 20 24 28 32 36 40A

0.75

0.80

0.85

0.90

0.95

1.00

Output Current