Hold-up time – Rockwell Automation 1606-XLS960EE Power Supply Reference Manual User Manual

Page 8

Advertising
background image

All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

8

Rockwell Automation Publication 1606-RM029A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

7. Hold-up Time

AC 230V

Hold-up Time

typ.

58ms

at 24V, 20A, see Fig. 7-1

min.

47ms

at 24V, 20A, see Fig. 7-1

typ.

30ms

at

24V,

40A,

see

Fig.

7-1

min.

24ms

at 24V, 40A, see Fig. 7-1

Fig. 7-1 Hold-up time vs. input voltage

Fig. 7-2 Shut-down behavior, definitions

0

10

20

30

40

60ms

170

190

210

230

250Vac

Input Voltage

Hold-up Time

24V, 20A, typ.

24V, 40A, typ.

24V, 20A, min.

50

24V, 40A, min.

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Input