Operation on two phases, Use in a tightly sealed enclosure – Rockwell Automation 1606-XLS960EE Power Supply Reference Manual User Manual

Page 26

Advertising
background image

All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

26

Rockwell Automation Publication 1606-RM029A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

25.11. Operation on Two Phases

240V

+10%

max.

L2

L1

L3

L

N

PE

Power Supply

AC

DC

internal

fuse

The power supply can also be used on two-phases of a three-phase-system.
Such a phase to phase connection is allowed as long as the supplying voltage
is below 240V

+10%

.

25.12. Use in a tightly Sealed Enclosure

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.

The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.

The power supply is placed in the middle of the box, no other heat producing item is inside the box.

Enclosure:

Rittal Typ IP66 Box PK 9522 100, plastic, 254x180x165mm

Load:

24V, 32A; (=80%) load is placed outside the box.

Input:

230Vac

Temperature inside enclosure:

61.6°C (in the middle of the right side of the power supply with a distance of 2cm)

Temperature outside enclosure: 23.3°C
Temperature rise:

38.3K