Rockwell Automation 1606-XLE960MX-3N Power Supply Reference Manual User Manual

Page 11

Advertising
background image

All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM025A-EN-P — April 2014

11

Bulletin 1606 Switched Mode Power Supplies

14. EMC

The power supply is suitable for applications in industrial environments as well as in residential, commercial and light
industry environments without any restrictions. The CE Mark indicates conformance with EMC guideline 89/336/EC,
93/68/EC and the low-voltage directive (LVD) 73/23/EC. A detailed report is available upon request.

EMC Immunity

EN 61000-6-1, and EN 61000-6-2 Generic standards

Electrostatic discharge

EN 61000-4-2

Contact discharge
Air discharge

8kV
15kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz-1GHz

10V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

Input lines
Output lines

4kV
2kV

Criterion A
Criterion A

Surge voltage on input

EN 61000-4-5 L1
L1 / L2 / L3

+ -

2kV
4kV

500V

Criterion A
Criterion A

Criterion A

-

+

PE

Conducted disturbance

EN 61000-4-6

0.15-80MHz

10V

Criterion A

EMC Emission

EN 61000-6-3 and EN 61000-6-4 Generic standards

Conducted emission

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines

Class B, output lines

Radiated emission

EN 55011, EN 55022

Class B

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

Switching frequency

Switching frequency

36kHz

Nearly constant

EN 55022

L2, L2

L3, L1

L3

PE

Surge voltage on output

EN 61000-4-5

500V

Criterion A

Mains voltage dips EN 61000-4-11 0% of 400Vac 20ms Criterion B
40% of 400Vac 200ms Criterion C
70% of 100Vac 500ms Criterion C
0% of 480Vac 20ms Criterion B
40% of 480Vac 200ms Criterion C
70% of 480Vac 500ms Criterion C

Power transients VDE 0160 over entire load range 1300V, 1.3ms Criterion D

Criteria:

A:

Power supply shows normal behavior within the defined limits.

B:

During the mains voltage dip, the output voltage will decrease according to curves in the Hold-up Time section. The unit works in

normal mode after the voltage dip. If criterion A is required, use 1606-XLSBUFFER48 module in addition to 1606-XLE power supply.

C:

Temporary loss of function is possible. Power supply may shutdown and restart by itself. No damage or hazard to the power supply occurs.

D:

The input transient blocker opens and the main converter is without input power during such transients. The output voltage decreases as

well, as described in the Hold-up Time section, during such an event.

Harmonic input current EN 61000-3-2 Fulfilled, active PFC

Voltage fluctuations, flicker EN 61000-3-3 Fulfilled