All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM025A-EN-P — April 2014

9

Bulletin 1606 Switched Mode Power Supplies

10. Functional Diagram

Fig. 10-1 Functional diagram

+

-

Active

Transient

Blocker

Input
Filter

Input

Rectifier

Reset

Output

Voltage
Monitor

Over-

Voltage

Protection

Output

Power

Manager

Temp.

Shut-

down

Input

Voltage
Monitor

L3

L2

L1

Semi-

regulated

Power

Converter

Output

Filter

DC-ok

LED

Warning

LED

Shut-down

LED

11. Front Side and User Elements

Fig. 11-1 Front side of 1606-XLE960MX-3N

A. Output Terminals
Large screw terminal

+ Positive output
- Negative (return)
output


See section 12
“Terminals and
Wiring” to choose
appropriate wire size.

B. Input Terminals
Screw terminals
L1, L2, L3:

Line inputs

PE (Protective

Earth) input

C. DC-ok LED (green)

Indicates a normal operation. The LED is on
if the output voltage is higher than 43.2V.
D. Warning LED (yellow)

- A steady-state light indicates an output

current higher than the nominal current
and that the internal shutdown timer is
running.

- A double flash indicates a phase-loss or

too low / too high input voltage.

(< 3x400Vac or > 3x560Vac)

- A fast flash warns of an impending

temperature shut-down. A shut-down
can be expected within 10 minutes, if
the ambient temperature or the load
current stays constant.

E. Shut-down LED (red) and reset button F.
The red LED flashes when the device has
shut down. Pressing the reset button or
cycling the input power (10s required)
initiates a restart. When the fault is
cleared, the device will operate normally.