All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM025A-EN-P — April 2014

17

Bulletin 1606 Switched Mode Power Supplies

25. Application Notes

25.1. Periodical Peak Power Capability

Fig. 25-1 Periodical peak power capability

The short term power can be used
periodically.
The duration of the peak power (TP

)

must be shorter than 15s.
The time between two peak power
pulses must be three times longer than
the duration of the preceding pulse
length.

t

T

100%

125%

P

OUT

P

NOM

T

P

> 3x T

P

25.2. Charging of Batteries

The power supply shall not be used to charge batteries.