Advertising
All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM025A-EN-P — April 2014
17
Bulletin 1606 Switched Mode Power Supplies
25. Application Notes
25.1. Periodical Peak Power Capability
Fig. 25-1 Periodical peak power capability
The short term power can be used
periodically.
The duration of the peak power (TP
)
must be shorter than 15s.
The time between two peak power
pulses must be three times longer than
the duration of the preceding pulse
length.
t
T
100%
125%
P
OUT
P
NOM
T
P
> 3x T
P
25.2. Charging of Batteries
The power supply shall not be used to charge batteries.