Output – Rockwell Automation 1606-XLE960MX-3N Power Supply Reference Manual User Manual

Page 6

Advertising
background image

All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

6

Rockwell Automation Publication 1606-RM025A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

7. Output

Output

voltage

nom.

48V

Output voltage adjustment range

none

The output voltage is fixed. No ajustment possible.

Output current

nom.

20A continuous,

see

Fig. 7-1

25A

up to 15s with full output voltage, see Fig. 7-1

Short-circuit current

typ.

90A

load impedance 50mOhm, see Fig. 7-1

Note: The short-circuit current is available for 0.1s.

Output

power

nom.

960W continuous

1200W up

to

15s

Line

regulation

max.

±2% see

Fig. 5-1

Load

regulation

max.

1600mV

static value, 0A 20A

0A

max.

100mV static

value,

2.5A

20A

2.5A

Ripple and noise voltage *)

max.

2500mVpp 20Hz-2kHz,

50Ohm

max.

300mVpp

2kHz to 20MHz, 50Ohm

Output

capacitance

typ.

7 600μF

*) The ripple and noise voltage mostly consist of a mains ripple with 300Hz (50Hz mains) or 360Hz (60Hz mains). The ripple and
noise voltage can be reduced by the utilization of external capacitors.

The power supply is also designed to support loads with a higher short-term current and power requirement. The
short-term duration is firmware controlle d by an output power manager. If the nominal output power is exceeded for
a certain period of time which is defined in zone A, B and C, the power supply responds with an automatic shut-down.
Pressing the reset button or cycling the input power (10s off time is required) initiates a restart attempt. If the fault has
been cleared the device will operate normally.
The short term power can be used periodically . See section 25.1 for further information.

Fig. 7-1

Output voltage vs. output current, typ.

V

OUT

20A

A

0

7

A

5

2

40A

0

A

15s

48V

100A

30A

A

0

9

A

0

8

A

0

6

A

0

5

A

0

1

24V

I

OUT

B

5s

C

0.1s

3x 408V
3x 480V
3x 552V

1606-XLE960MX-3N

Zone A

:

25% extra output power for typ. 15s

Zone B

:

100% higher output current for typ. 5s

Zone C: Quick-acting shut-down after typ. 0.1s

Advertising