Ac-input – Rockwell Automation 1606-XLE960MX-3N Power Supply Reference Manual User Manual

Page 4

Advertising
background image

All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

4

Rockwell Automation Publication 1606-RM025A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

5. AC-Input

1606-XLE960MX-3N

AC

input

nom.

3AC 480V

Mains

arrangement

TN-, TT- or IT-Mains. Consult factory if one phase is grounded.

AC input range

min.

3x 432-528Vac

fully regulated output (±2%), Pout > 48W

min.

3x 360-552Vac

*)

permanently allowed,

see Fig. 5-1 for output voltage regulation

max.

3x 565Vac Absolute maximum input voltage with no

damage to the power supply. Output
might be off at this level.

Input

frequency

nom.

50 – 60Hz

±6%

Turn-on

voltage

typ.

3x 390Vac

see Fig. 5-2

Shut-down

voltage

typ.

3x 355Vac

see Fig. 5-2

Input

current

nom.

1.4A

at 20A, symmetrical input, see Fig. 5-4

Power

factor

**)

typ.

0.93

at 20A, symmetrical input, see Fig. 5-5

Turn-on

overshoot

typ.

1000mV

see Fig. 5-3

Start-up delay ***)

typ.

350ms

over the entire load range, see Fig. 5-3

Rise

time

typ.

40ms 0mF, 20A, see Fig. 5-3

typ.

70ms 20mF, 20A, see Fig. 5-3

*)

A minimum voltage of 3x408Vac is required to turn the power supply on.

**)

The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.

***)

The start-up delay for mains voltage interruptions up to 350ms is close to zero. In such cases, the power supply will

immediately generate the output voltage once the mains voltage interruption is over. Do not use the buffer module
1606-XLSBUFFER48 as an accessory when longer mains interruptions need to be bridged (see section 24).


Input Voltage Range

Fig. 5-1

Output voltage vs. input voltage and input current

Changes of the input voltage will be fully
regulated within certain limits. The
output voltage will only start to change
proportionally to the input voltage with
extreme under or over-voltages. The
yellow LED reports an input voltage
problem if exceeded by a window of
±15%. The maximum increase of the
output voltage is limited to the 57.2V
OVP level. This level will be kept
regulated for 2s before the power supply
will shut down and re ports “Shut-down”
by the red LED.

48V

40V

52V

44V

504

456

576Vac

384

V

OUT

V

IN

480

56V

528 552

432

408

360

P

OUT

> 48W (>5%)

P

OUT

= 0W

Advertising