All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

Rockwell Automation Publication 1606-RM017A-EN-P — February 2014

11

Bulletin 1606 Switched Mode Power Supplies

10. Efficiency and Power Losses

Efficiency typ.

97.5%

Normal

mode,

24V

10A, 12V 0A, battery fully charged

typ.

96%

Normal mode, 24V 7.0A, 12V 5A, battery fully charged

Power losses

typ.

3.4W

Normal mode, no load, battery fully charged

typ.

6W

Normal mode, 24V 10A , 12V 0A, battery fully charged

typ.

10W

Normal mode, 24V 12.3A, 12V 5A, battery fully charged

typ.

5.5W

During battery charging, no load.

typ.

19W

Buffer mode, 24V 10A, 12V 0A

typ.

23W

Buffer mode, 24V 7.0A, 12V 5A

11. Functional Diagram

Fig. 11-1 Functional Diagram

DC-UPS Control Unit

Battery

Charger

Battery

Tester

Cut-off

Relay

Battery

+

-

12V Battery

24V

Power

Supply

Input

-

+

-

+

Reverse

Polarity

Protection

Input Fuse

&

*

Electronic

Current

Limiter

Buffered

Load

+

-

24V Output

Step-up

Converter

Step-down

Converter

+

-

(5)

(6)

Ready

Contact

(1)

(2)

Buffering

Contact

(3)

(4)

Controller

Diagnosis LED (yellow)

Check Wiring LED (red)

Status LED (green)

Buffer-time Limiter

10s, 30s, 1m, 3m, 10m,

End-of-charge Voltage

Inhibit -

Inhibit +

Replace

Battery

Contact

(7)
(8)

12V Output

Buffered

Load

*)

Return current protection: this feature uses a Mosfet instead of a diode in order to minimize the voltage drop and power

losses.