Front side user elements – Rockwell Automation 1606-XLS240UPSD Power Supply Reference Manual User Manual

Page 14

Advertising
background image

All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

14

Rockwell Automation Publication 1606-RM017A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

14. Front Side User Elements

A Power

Port

Quick-connect spring-clamp terminals, connection for input voltage,
output voltage and battery. The 12V power port is placed on the bottom.

B Signal Port

Plug connector with screw terminals, inserted from the bottom.
Connections for the Ready, Buffering, Replace Battery relay contacts and
for the Inhibit input. See details in section 13.

C Green Status LED
Ready:

Battery is charged > 85%, no wiring failure is recognized, input

voltage is sufficient and inhibit signal is not active.

Charging:

Battery is charging and the battery capacity is below 85%.

Buffering:

Unit is in buffer mode.

Flashing pattern of the green status LED:

Ready

Charging

Buffering

ON
OFF

ON
OFF

ON
OFF

D Yellow Diagnosis LED
Overload:

Output has switched off due to long overload in buffer mode

or due to high temperatures.

Replace

battery:

Indicates a battery which failed the battery quality test

(SoH test). Battery should be replaced soon.

Buffer-time

expired:

Output has switched off due to settings of Buffer-

timer Limiter. This signal will be displayed for 15 minutes.

Inhibit

active:

Indicates that buffering is disabled because of an inactive

inhibit signal.

Flashing

pattern

of

the

yellow diagnosis LED:

Overload

Replace

Battery

Buffer time

expired

Inhibit

active

ON
OFF

ON
OFF

ON
OFF

ON
OFF

E Red Check Wiring LED

This LED indicates a failure in the installation (e.g. input voltage excessively low), wiring, battery or battery fuse.

F Buffer-time

Limiter:

User accessible dial which limits the maximum buffer time in a buffer event to save battery energy. When the

battery begins to recharge after a di scharging event, the process is completed much faster since only the energy
which was taken out of the battery needs to be “refilled”. The following times can be selected: 10 seconds, 30
seconds, 1 minute, 3 minutes, 10 minutes or infinity (until battery is flat) which allows buffering until the deep
discharge protection stops buffering.

G End-of-charge

Voltage

Selector:

The end-of-charge-voltage shall be set manually according to the expected temperature in which the battery is

located. The dial on the front of the unit allows a continuous adjustment between +10 and +40°C. 10°C will set
the end-of-charge-voltage to 13.9V, 25°C

13.65V and 40°C

13.4V. If in doubt about the expected temperature,

set the unit to 35°C.

A

B

C

D

E

F

G