Output in buffer mode – Rockwell Automation 1606-XLS240UPSD Power Supply Reference Manual User Manual

Page 6

Advertising
background image

All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

6

Rockwell Automation Publication 1606-RM017A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

7. Output in Buffer Mode


If the input voltage falls below the transfer threshold level, the DC-UPS starts buffering without any interruption or
voltage dips. The transfer threshold level is typically 80mV higher than the 24V output voltage in buffer mode.
Buffering is possible even if the battery is not fully charged.

24V Output

Output voltage

nom.

DC 24V

Output is stabilized and independent from battery voltage.

22.45V

±1%, at no load,

22.25V

±1%, at 10A output current


Ripple and noise voltage

max.

20mVpp

20Hz to 20MHz, 50Ohm

Output current

nom.

0 - 10A

Continuously allowed, 12V output not loaded.

10 - 15A

*) 12V output not loaded.

min.

7.0A

If 12V output is loaded with 5A.


Short-circuit current

min.

17.9A

Load impedance 100mOhm **); the 12V output is off during an
overload or short on the 24V.

max. 21A

12V Output

Output voltage

nom.

DC 12V

Output is stabilized and independent from battery voltage.

Output voltage tolerance

±2%

Ripple and noise voltage

typ.

30mVpp

20Hz to 20MHz, 50Ohm ;

nom.

0 - 5A

Continuously allowed, may be lower if the 24V output is loaded
more than 7.0A

Output current

Short-circuit current

min.

4A

Load impedance 100mOhm, see Fig. 7-5

for typical values.

Continuous constant; the 24V output is on during an overload
or short on the 12V as long as the battery delivers current.

max. 5.5A

*)

If the output current is in the range between 10A and 15A (Bonus Power) for longer than 5s, a hardware-controlled

reduction of the maximal output current to 10A occurs. If the 10A are not sufficient to maintain the 24V, buffering stops at
both outputs after another 5s. Buffering is possible again as soon as the input voltage recovers.

**)

If the nominal output voltage cannot be maintained in buffer mode, the DC-UPS switches off after 5s to save battery
capacity.

Fig. 7-1 Buffering transition, definition

Fig. 7-2 Transfer behavior, typ.

Buffer mode

Output
voltage

24V

28V

Input
voltage

t

t

Transfer

threshold

5 00 m s /D IV

0 V

Ou t pu t
V o lt a g e

In p u t V o lt a g e

2 4V

2 2. 25 V a t 1 0A

2 4V