15. Terminals and Wiring

12V Terminal

Signal terminals

Power terminals
(except 12V)

Type Bi-stable,

quick-connect

spring-clamp terminals.
Shipped in open position.

Lockable plug connector
with spring-clamp
terminals.

Plug connector with screw
terminal. Shipped in open
position. To meet GL
requirements, unused terminal
compartments should be closed.

Solid wire

0.5-6mm

2

2

2

0.1-2.5mm

0.2-1.5mm

2

2

2

Stranded wire

0.5-4mm

0.1-2.5mm

0.2-1.5mm

AWG 20-10AWG

28-12AWG

22-14AWG

Ferrules

Allowed, but not required

Allowed, but not required

Allowed, but not required

Pull-out force

10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N
according to UL486E

Not applicable

Recom. screwdriver

Not required

3,5mm slotted

3,5mm slotted

Tightening torque

Not applicable

Not applicable

0.4Nm, 3.5lb.in

Wire stripping length

10mm / 0.4 in.

8.5mm / 0.34 in.

6mm / 0.24 in.

Fig. 15-1 Spring-clamp terminals, connecting a wire

1. Insert the wire

2. Close the lever

To disconnect wire:

reverse the procedure

Instructions:

a)

Use appropriate copper cables, that are designed
for an operating temperature of 60°C

b)

Follow national installation codes and regulations!

c)

Ensure that all strands of a stranded wire are properly
inserted in the terminal connection!

d)

Up to two stranded wires with the same cross section
are allowed in one connection point.