Reliability – Rockwell Automation 1606-XLS240UPSD Power Supply Reference Manual User Manual

Page 16

Advertising
background image

All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

16

Rockwell Automation Publication 1606-RM017A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

16. Reliability

Lifetime expectancy, normal mode

min.

114 000 h

At 10A output current, 40°C

min.

148 000 h

At 5A output current, 40°C

min.

380 000 h

At 10A output current, 25°C

MTBF SN 29500, IEC 61709, normal mode

788 000 h

At 10A output current, 40°C

MTBF MIL HDBK 217F, normal mode

343 000 h

At 10A output current , 40°C, ground benign GB40

The

Lifetime expectancy

shown in the table indicates the operating hours (service life) and is determined by the

lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours.
Lifetime expectancy is calculated according to the capacitor’s manufacturer specification. The prediction model allows
a calculation of up to 15 years from date of shipment.
MTBF

stands for

Mean Time Between Failures

which is calculated according to statistical device failures and indicates

reliability of a device. It is the statistical representation of the likelihood of failure of a unit and does not necessarily
represent the life of a product.