All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

2

Rockwell Automation Publication 1606-RM017A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

DC-UPS, Dual Output

24V DC-UPS With an Additional 12V Output for

Various Applications

Only One 12V Battery Required

Stable Output Voltage in Buffer Mode

Superior Battery Management for Longest Battery Life

Comprehensive Diagnostic and Monitoring Functions

Replace Battery Signal Included

Electronically Overload and Short Circuit Protected

50% Power Reserves

3 Year Warranty

1.

Description

2.

Specification Quick Reference

Input voltage

24Vdc

Nominal

22.5-30Vdc Input

range

Output voltage
(normal mode)

0.23V lower as
input voltage

Typ., 24V output

12V

12V

output

Output voltage
(buffer mode)

22.25V
12V

24V output at 10A
12V output at 5A

Output current
(normal mode)

0 - 15A
0 - 5A

24V output
12V output

Output current
(buffer mode)

0 - 10A
10 – 15A for 5s
0 - 5A

24V output
24V output
12V output

Total output

power

360W
240W

Normal mode
Buffer mode

Allowed batteries

3.9Ah to 40Ah

VRLA lead acid

Temperature range -25 to +70°C

Operational

Derating 6W/°C +50

to

+70°C

Dimensions 49x124x117mm

WxHxD

typ. 6’30”

7Ah battery module

24V 7A, 12V 5A

Buffer time

typ. 54’

26Ah module
24V 7A, 12V 5A

The 1606-XLS240-UPSD uninterruptible power
supply (UPS) controller along with a standard 24V
power supply and one 12V battery can bridge power
failures or voltage fluctuations. This unit can supply
and bridge both a 24V load as well as a 12V load at
the same time. The 12V is generated by a DC/DC
converter from the 24V output. Therefore, systems that
use 24V control circuits and require 12V for e.g.
remote radio telemetry can be supplied with
only one 1606-XLS240-UPSD DC-UPS controller.

The DC-UPS includes a professional battery
management system which charges and monitors
the battery to achieve the longest battery service life
as well as many diagnostic functions that ensure a
reliable operation of the entire system.

24V

Power

Supply

12V Battery

1606-
XLS240-
UPSD

DC-UPS

Dual

output

24V

Load

AC

24VDC

e.g.: PLC

e.g.: radio

transmitter

12V

Load

12VDC

3.

Catalog Numbers

4.

Certification Marks

DC-UPS

1606-XLS240-UPSD

24V and 12V output

IND. CONT. EQ.

UL 508

UL 60950-1

EMC, LVD

Accessories

1606-XLSBATBR1

1606-XLSBATASSY2
1606-XLSBARBR2

1606-XLB

Battery module 12V 7Ah
Mounting kit w/o battery

Battery module 12V 26Ah
Mounting kit w/o battery

Panel/Wall mount bracket

Marine RINA

GOST R

C-TICK

1606-XLSBATASSY1

Advertising