1329I-5.0 Integrated Drive/Motor — January, 1999

Chapter

6

Step 6 - Install a Hardwired Stop

Depending upon the requirements of the application, the 1329I unit can be set up to
provide either a coast-to-rest (default) or a ramp-to-rest (user option) operational stop.
The unit’s Function Loss input provides an additional coast-to-rest operational stop.

In addition to the operational stop, the user must provide a hardwired stop external to
the unit. The hardwired stop circuit must contain only hardwired electromechanical
components. Operation of the hardwired stop must not depend on electronic logic
(hardware or software) or on the communication of commands over an electronic
network or link.

ATTENTION: The user must provide an external, hardwired stop circuit
outside of the 1329I unit circuitry. This circuit must disable the system
in case of improper operation. Uncontrolled machine operation may result
if this procedure is not followed. Failure to observe this precaution could
result in bodily injury.