Diagnostics and Troubleshooting

1329I-5.0 Integrated Drive/Motor — January, 1999

Observe the following precautions when troubleshooting the unit:

• Stop the unit using either the Stop input or Function Loss input.

• Disconnect, tag, and lockout AC power before working on the unit.

• Verify that there is no voltage present at AC input terminals R/L1, S/L2, and T/L3.

Refer to Figure 5.2 for the location of the terminals.

• Wait five minutes and verify that the DC bus has discharged to zero volts. See

Figure 5.2 for the location of the DC bus test points.

11.1 Fault Codes and Corrective Actions

The following table describes normal operational faults that may be corrected by the
user. For standard units, the corrective action assumes that a Reset pushbutton is wired
between control terminals 15 and 13, as described in Section 7.8.

If a fault occurs, do the following:

1. Try to clear the fault first by pressing the Reset pushbutton (or

key on local

operator control units). If the fault reoccurs, continue with Step 2.

2. Refer to Table 11.1 to identify the fault code and the possible causes.

3. Perform the corrective action(s).

4. Clear the fault by pressing the Reset pushbutton (or

key).

Table 11.1
Fault Codes and Corrective Actions

RESET

RESET

Code

Fault Description

Fault Cause

Corrective Action

Keypad Cable Disconnected

Keypad cable disconnected while
unit under power.

Turn off power to the unit. Verify the
keypad cable connection. Turn
power on to the unit.

Keypad Cable Connected

Keypad cable connected while unit
under power.

Turn off power to the unit. Verify the
keypad cable connection. Turn
power on to the unit.

Function Loss

Open connection on Function
Loss control terminal block inputs
(terminals 7 and 11).

Check and restore the Function
Loss connection on the control ter-
minal block (see Section 7.1).
Check the external sensors wired
into the Function Loss string.

High Bus Voltage

High input line.

Deceleration time too fast.

Overhauling load.

Check input line to verify voltage is
within operating specifications.

Increase deceleration time using
the accel/decel rotary switch (see
Section 8.2).

or