Rockwell Automation Publication 1609-QS002A-EN-P - May 2014

19

Ethernet Mode Setup

Chapter 2

6. Go to the "Controller Scope Tags" and identify your UPS ENET card input/output/configuration tags. Change the

"XXXX:C.Data[0].0" tag from 0 to 1. Note: XXXX is a unique name given to the UPS ENET card. ENET_Card
was the name given in this example, therefore the full tag name is "ENET_Card:C.Data[0].0"

7. Reset the card by pressing the black circle button on the card. Wait approximately 45 seconds until communications

are established. You should have an "IO OK" and the yellow triangle in the module should be gone.

 

 