Rockwell Automation Publication 1609-QS002A-EN-P - May 2014

Appendix B

EtherNet/IP Parameters

32

Required

Get

V

TestResultsSummary

INT

The results of the current or last UPS diagnostics
test performed. The values for donePass(1),
generalTestFail(3), and batteryTestFail(4) indicate
that the test completed either successfully, with a
warning, or with an error, respectively. Tests
which have not yet concluded are indicated by
inProgress(2). The value noTestsInitiated(0)
indicates that no previous test results are
available.

noTestsInitiated(0),
donePass(1),
inProgress(2),
generalTestFail(3),
batteryTestFail(4),
deepBatteryTestFail(5)

33

Required

Get

V

Alarm

DWORD

UPS Alarm status

off(0),on(1)

Disconnect

bit 0

Does the UPS disconnect?

PowerFail

bit 1

Does the input power fail?

BatteryLow

bit 2

Are the UPS batteries low?

LoadWarning

bit 3

Does the UPS load percent over the load warning
value?

TestInProgress

bit 4

Does the UPS test in progress?

BatteryTestFail

bit 5

Does the UPS test fail?

OutputOverload

bit 6

Does the UPS output overload?

InverterAbnormal

bit 7

Does the UPS inverter abnormal?

ReserveAbnormal

bit 8

Does the UPS reserve abnormal?

OverTemperature

bit 9

Does the UPS overheat?

OutputBad

bit 10

Is the UPS output abnormal?

UPSOff

bit 11

Is the UPS in standby mode?

ChargerFail

bit 12

Does the UPS charger fail?

FanFail

bit 13

Does the UPS fan fail?

OutputOff

bit 14

Indicates whether the UPS output is turned off or
not

SmartShutdown

bit 15

Indicates whether the Smart Shutdown is in
progress

UPSShutdown

bit 16

UPS shutdown

Reserved

bit 17-31

Reserved for future use and shall be set to zero

UPS Object (0x377)
Attribute ID Need

Access Rule

NV

Name

Data Type

Description of Attribute

Semantics of value