Rockwell Automation 1609-ENET Ethernet Network Card Quick Start User Manual

Page 26

Advertising
background image

26

Rockwell Automation Publication 1609-QS002A-EN-P - May 2014

Appendix B

EtherNet/IP Parameters

UPS Object (0x377)
Attribute ID Need

Access Rule

NV

Name

Data Type

Description of Attribute

Semantics of value

1

Required

Get

NV

Output Rating

STRUCT of:

The magnitude of the nominal output

NV

VA

INT

VA rating

NV

Voltage

INT

Voltage rating

NV

Frequency

INT

Frequency rating

2

Required

Get

NV

Input Rating

STRUCT of:

The magnitude of the nominal input

NV

Voltage

INT

Voltage rating

NV

Frequency

INT

Frequency rating

3

Required

Get

NV

RatingBatteryVoltage

INT

The magnitude of the nominal battery
voltage rating

4

Required

Get

NV

LowTransferVoltage

STRUCT of:

The Setup of low line input voltage that allowed
the UPS system transfers to the battery source

NV

UpBound

INT

The maximum voltage limited for the
LowTransferVoltage

NV

LowBound

INT

The minimum voltage limited for the
LowTransferVoltage

5

Get

NV

HighTransferVoltage

Array of
STRUCT of:

The Setup of high line input voltage that allowed
the UPS system transfers to the battery source

NV

UpBound

INT

The maximum voltage limited for the
HighTransferVoltage

NV

LowBound

INT

The minimum voltage limited for the
HighTransferVoltage

6

Required

Get

NV

UPS Type

INT

Indicate the UPS type

on-line(1)
off-line(2),
line-interactive(3),
three-phase(4),
splite-phase(5)
All other values
reserved

7

Required

Get/Set

NV

AutoReboot

INT

In backup mode, the UPS may shutdown normally
by SDA command, dry-contact remote shutdown
signal or low battery shutdown. This command is
used to determine the unit should restart or not
next time when the power restores

on(1),
off(2)
All other values
reserved

8

Required

Get/Set

V

ShutdownAction

INT

If the value is greater than 0 the UPS performs
shutdown action that defined by ShutdownType
after the seconds. 0, aborted

9

Required

Get/Set

V

RestartAction

INT

UPS will restart after the indicated number
of minutes.
-1, aborted

10

Required

Get/Set

NV

BuzzerAlarm

UINT

UPS will keep silence but will alarm again when
next power event is occurred

alarm(1),
silence(2)

11

Required

Get/Set

NV

BuzzerState

INT

If it is disabled then the UPS is always muted

enable(1),
disable(2)

12

Required

Get/Set

NV

Sensitivity

INT

The sensitivity of the UPS to utility line
abnormalities or noises

normal(0),
reduced(1),
low(2)

13

Required

Get/Set

NV

LowVoltageTransferPoint

INT

The input minimum line voltage allowed before
the UPS system transfers to battery backup

14

Required

Get/Set

NV

HighVoltageTransferPoint

INT

The input maximum line voltage allowed before
the UPS system transfers to battery backup

15

Required

Get/Set

V

ShutdownOSDelay

INT

The operating system shutdown delay time when
the input power fail

16

Required

Get/Set

NV

UPSBootDelay

UINT

Delay the UPS startup after power restores.
The power quality may not stable when power
restores, this feature let the UPS wait a period
of time to startup the system

17

Required

Get/Set

NV

ExternalBatteryPack

INT

Indicate the number of external battery pack

18

Required

Get

V

InputNumLines

INT

The number of input lines utilized in this device

Limited 1